Permit: T07CM03463

Parcel: 14122004R


Addresses:

8500 S RITA RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/21/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DESIGNATION ON PLAN DOES NOT MATCH FIELD CONDITIONS
2. NEED OVERCURRENT PROTECTION ON XFMR SECONDARIES TO PANEL - NEC 240.21
3. NEED GROUNDING ELECTRODE SYSTEM AT SOLAR TEST FIELD PER - NEC 250.32
4. CAN ONLY FEED TEST FIELD WITH ONE BRANCH CIRCUIT
OR FEEDER - NEC 225.30
5. NEED DISCONNECTING MEANS AT TEST FIELD PER
NEC 225.31, 225.32
6. NEED LABELING @ TEST FIELD PER NEC 690
7. ALL PV SYSTEM DISCONNECTS TO BE GROUPED - NEC 690.14
8. WORK NOT COMPLETE