Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DESIGNATION ON PLAN DOES NOT MATCH FIELD CONDITIONS 2. NEED OVERCURRENT PROTECTION ON XFMR SECONDARIES TO PANEL - NEC 240.21 3. NEED GROUNDING ELECTRODE SYSTEM AT SOLAR TEST FIELD PER - NEC 250.32 4. CAN ONLY FEED TEST FIELD WITH ONE BRANCH CIRCUIT OR FEEDER - NEC 225.30 5. NEED DISCONNECTING MEANS AT TEST FIELD PER NEC 225.31, 225.32 6. NEED LABELING @ TEST FIELD PER NEC 690 7. ALL PV SYSTEM DISCONNECTS TO BE GROUPED - NEC 690.14 8. WORK NOT COMPLETE |