Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03453

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. EMERGENCY LIGHTING NOT PER PLAN, NOT WORKING, TO BE ENERGIZED BY NORMAL LIGHTING CKT FOR THAT AREA
NEC 700.12
2. FIRE ALARM NOT COMPLETED
3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4
4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS, EMT WITHIN 36", PROTECT MC FROM PHYSICAL DAMAGE - NEC 330
5. ALL METAL BOXES TO BE GROUNDED, PLANS ALSO REQUIRE ISOLATED GROUND TO CASH WRAP, MAKE SURE WIRING PER PLAN, CONDUCTORS PROPERLY IDENTIFIED
6. DATA PHONE NOT COMPLETE/REMOVE UNUSED L.V WIRING