Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03453
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. EMERGENCY LIGHTING NOT PER PLAN, NOT WORKING, TO BE ENERGIZED BY NORMAL LIGHTING CKT FOR THAT AREA NEC 700.12 2. FIRE ALARM NOT COMPLETED 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4 4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS, EMT WITHIN 36", PROTECT MC FROM PHYSICAL DAMAGE - NEC 330 5. ALL METAL BOXES TO BE GROUNDED, PLANS ALSO REQUIRE ISOLATED GROUND TO CASH WRAP, MAKE SURE WIRING PER PLAN, CONDUCTORS PROPERLY IDENTIFIED 6. DATA PHONE NOT COMPLETE/REMOVE UNUSED L.V WIRING |