Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03453
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL AND HARD LID COVER |
|
11/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE INSULATION UNDERGROUND SCREWS 2. SELF-TAP SCREW NOT ALLOWED FOR GROUND CONNECTION 3. STRAP FLEX WITHIN 12" OF BOXES 4. IDENTIFY WHITE USED AS HOT IN SWITCH LEG - WHITE CONDUCTOR TO BE FED TO SWITCH 5. INSTA-HOT TO BE DEDICATED CKT 6. ENTRY SOFFIT J-BOXES TO BE ACCESSIBLE FROM OPENING 7. 4 1/16 BOX OVERFILLED, UNGROUNDED PARTIAL INSPECTION ELECTRICAL CONTRACTOR TO GO THROUGH WORK TO INSURE IT COMPLIES WITH PLAN AND NEC |