Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSP. |
|
| 11/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE CONTRACTOR ON SITE TO OPEN EQUIPMENT FOR INSPECTION 2. DO NOT HAVE CLEAR WORKING SPACE IN FRONT OF XFMR AND DISCONNECT - NEC 110 3. SERVICE LOCKED BEHIND GATE AT SCHOOL 4. NEED TO PROVIDE DISCONNECT FOR FEEDER TO CELL STRUCTURE AT CELL STRUCTURE - NEC 225 5. INSTALL PROTECTIVE BUSHING FOR CONDUCTORS #4 & LARGER NEC 300 6. INSTALL GROUNDING ELECTRODE SYSTEM FOR CELL STRUCTURE DISCONNECT NEC 250 7. GROUNDING CONDUCTORS/BONDING CONDUCTORS NOT SIZED PER PLAN OR NEC 8. THIS MAY NOT BE COMPLETE LIST |
|
| 11/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |