Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03444
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. METAL EXTENDER RINGS NOT APPROVED 2. PLANS NEED CITY STAMP FOR APPROVAL |
|
03/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE AND/OR MORE THAN 1/8" AROUND - 314.20, 314.21 2. PANEL DIRECTORY TO BE AS PER 408.4 NO ABBREVIATIONS 3. WHERE IS CLOSET LIGHT & SWITCH ON PLANS 4. LIGHTING FOR EM & EXIT IN BACK ROOM NOT AS PER PLANS OR 700.12 5. WATER HEATER TO HAVE DISCONNECTING MEANS AND CORRECTLY LABELED AT PANEL - NOT AN INSTA-HOT 6. PANEL "LB" DOES NOT MATCH PLANS 7. SERVICE DISCONNECT MISSING SERIES RATING LABELS AS PER PLAN AND LABEL TO MATCH INTERIOR PANELS. |