Permit: T07CM03444

Parcel: 12708187F


Addresses:

5441 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM03444

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
02/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH VDV CABLING 300.11
02/08/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
02/07/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLE AS PER 300.11 ALSO VDV CABLING
2. SUPPORT WIRES NEEDED ON ALL FIXTURES
3. PROPERLY SUPPORT VDV CABLING - NOT TIED TO SPRINKLER PIPES OR TUCKED UNDER CONDUITS
4. ATTACH FIXTURES TO GRID 410.16
5. FILL UNUSED OPENINGS
6. GROUND JUNCTION BOXES - 230.148
7. LEAVE ALL CEILING BOXES OPEN TO INSPECT