Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03444
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AFTER CORRECTIONS REVISION WORK 1. STRAP MC CABLES 2. PLANS DO NOT ALLOW PVC UP WALLS - CHANGE TO EMT |
|
01/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & CANS AFTER VDV IS CORRECTED 1. FINISH SUPPORTING VDV CABLING AS DISCUSSED |
|
01/04/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN LOOSE FITTINGS 2. SUPPORT VDV CABLING PER 725.6, 800.24, 300.11 * RECEIVED LETTER MC CABLE |
|
12/27/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) M/C CABLE TO TERMINATE 2) USE APPROVED STRAPS FOR M/C CABLE 3) OK 8 FLOOR BOXES |
|
12/26/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) USE APPROVED STRAPS FOR M/C CABLE AND STRAP WITHIN 12" OF BOXES 2) SUPPORT CONDUITS PER CODE 3) SPECS ARE NOT CLEAR IF PVC AND FLOOR BOXES ARE ALLOWED ALSO IF M/C CABLE CAN BE USED-PLEASE HAVE ENGINEER CLARIFY 4) PLEASE ADD 02010 TO PERMIT 5) FINISH WEST WALL |