Permit: T07CM03444

Parcel: 12708187F


Addresses:

5441 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03444

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
AFTER CORRECTIONS
REVISION WORK

1. STRAP MC CABLES
2. PLANS DO NOT ALLOW PVC UP WALLS - CHANGE TO EMT
01/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & CANS AFTER VDV IS CORRECTED

1. FINISH SUPPORTING VDV CABLING AS DISCUSSED
01/04/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS
2. SUPPORT VDV CABLING PER 725.6, 800.24, 300.11

* RECEIVED LETTER MC CABLE
12/27/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) M/C CABLE TO TERMINATE
2) USE APPROVED STRAPS FOR M/C CABLE
3) OK 8 FLOOR BOXES
12/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) USE APPROVED STRAPS FOR M/C CABLE AND STRAP WITHIN 12" OF BOXES
2) SUPPORT CONDUITS PER CODE
3) SPECS ARE NOT CLEAR IF PVC AND FLOOR BOXES ARE ALLOWED ALSO IF M/C CABLE CAN BE USED-PLEASE HAVE ENGINEER CLARIFY
4) PLEASE ADD 02010 TO PERMIT
5) FINISH WEST WALL