Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE AND SHEETROCK 2) USE GREEN GROUNDING SCREW IN METAL BOXES 3) SEPERATE NEUTRAL AND GROUNDING BARS IN SUB PANEL BEFORE FINALS |
|
| 07/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BLOCK BATH CEILING REGISTER BOX 2) INSTALL ROMEX CONNECTORS ON METAL BOXES AND GROUND METAL BOXES 3) MAKE UP GROUND WIRES IN ALL BOXES 4) NAIL STOP ALL WIRES WITHIN 1 1/2" OF SURFACE 5) BATH GFI TO BE SEPERATE 20 AMP CIRCUIT 6) DO NOT INTERMIX #12 AND #14 WIRE ON SAME CIRCUIT 7) OK TO SHEETROCK DUCT IN HOUSE |