Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM03416
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL AIR BALANCE OK |
|
05/07/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* BUILD CONDENSATE TRAPS PER MANUFACTURERS INSTALL INSTRUCTIONS. PAINT EXPOSED PVC W/LATEX PAINT MARK UNIT DATA PLATES W/PROPER HEAT STRIP AND FUSE ACCORDINGLY. SUPPORT CONDENSATE PIPING EVERY 4' PROVIDE A 90 DEG. ELBOW AT CONDENSATE TERMINATION PROVIDE AIR BALANCE REPORT |