Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03416
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/09/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WAITING ON LETTER 2. ALL UNLISTED EQUIPMENT HAS BEEN REMOVED FROM JOB SITE AT THIS TIME. |
|
05/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VERIFY LISTING FOR HAIR DRYERS 2. WAITING ON LETTER FOR STEAM GENERATORS |
|
05/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH STEAM GENERATOR 2. VERIFY LISTING FOR TOWEL WARMERS 3. NEED PAPERWORK FOR FOOT MASSAGER TO VERIFY IF GFCI NEEDED 4. PROTECT SEAL TITE FROM SHARP METAL EDGES AT EXHAUST FANS |
|
05/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* * CHECK ROOF NEXT TIME 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR FLUSH AT COMBUSTIBLES - 314.20 2. VERIFY LISTING OF FACIAL STEAMERS 3. WATER HEATER FUSES TO BE PER AMPACITY OF CONDUCTORS 4. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS, DISTINGUISHABLE FROM ONE ANOTHER 5. EM & EXIT LTS. TO BE AS PER 700.12 6. INSTALL ALL OCCUPANCY SENSORS AS PER PLANS 7. PLEASE REVISE PLANS FOR LIGHTING AND ENERGY CALUC'S 8. DISCONNECT FOR STEAM GENERATOR NOT AS PLANS OR CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS. |