Permit: T07CM03416

Parcel: 114469380

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03416

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WAITING ON LETTER
2. ALL UNLISTED EQUIPMENT HAS BEEN REMOVED FROM JOB SITE AT THIS TIME.
05/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VERIFY LISTING FOR HAIR DRYERS
2. WAITING ON LETTER FOR STEAM GENERATORS
05/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH STEAM GENERATOR
2. VERIFY LISTING FOR TOWEL WARMERS
3. NEED PAPERWORK FOR FOOT MASSAGER TO VERIFY IF GFCI NEEDED
4. PROTECT SEAL TITE FROM SHARP METAL EDGES AT EXHAUST FANS
05/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
* CHECK ROOF NEXT TIME

1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR FLUSH AT COMBUSTIBLES - 314.20
2. VERIFY LISTING OF FACIAL STEAMERS
3. WATER HEATER FUSES TO BE PER AMPACITY OF CONDUCTORS
4. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS, DISTINGUISHABLE FROM ONE ANOTHER
5. EM & EXIT LTS. TO BE AS PER 700.12
6. INSTALL ALL OCCUPANCY SENSORS AS PER PLANS
7. PLEASE REVISE PLANS FOR LIGHTING AND ENERGY CALUC'S
8. DISCONNECT FOR STEAM GENERATOR NOT AS PLANS OR CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS.