Permit: T07CM03416

Parcel: 114469380

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T07CM03416

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2008 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
05/01/2008 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
OK TO ENERGIZE
RECEIVED CK#1682 FOR $225.00

1. BONDING JUMPERS TO BE SIZED PER 250.102 & 250.66
2. NEED REJECTION PINS & FUSES
3. FILL UNUSED OPENINGS IN PANELS
4. RECALL AFTER BONDING JUMPERS INSTALLED