Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2008 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 05/01/2008 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE RECEIVED CK#1682 FOR $225.00 1. BONDING JUMPERS TO BE SIZED PER 250.102 & 250.66 2. NEED REJECTION PINS & FUSES 3. FILL UNUSED OPENINGS IN PANELS 4. RECALL AFTER BONDING JUMPERS INSTALLED |