Permit: T07CM03416

Parcel: 114469380

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03416

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. STEAM ROOM FIXTURE TO BE FOR WET LOCATION
2. USE APPROVED STRAPS

OK WALLS AFTER CORRECTIONS
02/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WATER BOND TO BE ACCESSIBLE

OK EXTERIOR WALL EXCEPT AS NOTED
ROOM 103, 106, 107

*AGAIN: DO NOT ONE SIDE UNTIL CLEARED
01/10/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
DO NOT ONE SIDE
1. NO MORE THAN 360 DEG. IN CONDUIT RUNS
2. INSTALL ALL PLASTER RINGS
3. JUNCTION BOX TO BE ACCESSIBLE
4. PROTECT PVC CONDUITS AT BASE PLATE