Permit: T07CM03414

Parcel: 113095310

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OLD WIRING BEHIND NEW WALLS TO BE DE-ENERGIZED AND REMOVED, DEMO ALL OLD WIRING
2. USE ONLY BOXES LISTED FOR ROMEX ENTRY
3. NEED ADDITIONAL NAIL PLATES WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE
4. NEED MINIMUM #10CU FOR 30 AMP EQUIPMENT GROUND
5. ROMEX CONNECTORS TO BE USED FOR NUMBER OF CABLES THEY ARE LISTED FOR.