Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03408
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECEPTACLES IN SHOP AREAS TO BE AS PER 511.12 2. WAITING ON PLANS & REVISIONS 3. COMPRESSOR NOT LISTED |
|
| 10/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ARCHITECT NEEDS TO REVISE PANEL SCHEDULES & LOADS TO CORRILATE WITH LETTER 2. FINISH ITEMS #3,4,6,10,12,13 & 17 ADD COMPRESSORS TO LIST FOR LABELING OK ROOF |
|
| 10/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENINGS IN PANELS 2. MISSING SET SCREWS FOR FITTING 3. PLANS CALL FOR 3 PHASE HOISTS 4. PLEASE VERIFY AIR EXCHANGE FOR REPAIR SHOP AREA AND LOCATIONS PER 511 5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANEL 6. APPROVED EXTENDER RINGS NEEDED PER 314.20 *IF FLOOR IS RAISED ALSO 7. SWITCHES FOR HOIST TO BE MOTOR RATED 430.109 8. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11 9. SUPPORT FIXTURES PER 410.16 & AMENDMENT FOR SUPPORT WIRES 10. LABEL DISCONNECTING MEANS 11. CORDS NOT A PERMANENT WIRING METHOD FOR COMPRESSOR 400.7 & 8 CORDS UNDERSIZED FOR AMPACITY OF FUSES 12. MULTI-POLE TERMINATIONS AT GROUND LUG IN STARTERS 13. VERIFY LISTING LABELS ON WHEEL BALANCER, ALIGNMENT LIFT, LIGHT UP DISPLAY 14. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM FLOOR BOXES 15. SECURE SEALTITE TO STRUCTURE AT SERVICE 16. MISSING EM FLOOD IN BACK OUTSIDE 17. EXIT & EM LIGHTING TO BE AS PER 700.12 18. BOXES OVERFILLED 19. FILL OUT CIRCUIT DIRECTORY PANEL "P" * CHECK ROOF NEXT TIME |