Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07CM03406
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | ELECTRIC - UNDERGROUND | Approved | ||
03/18/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE PREVIOUS NOTES FOR CONDUIT/CABLE RUNS ACROSS PARKING LOT FROM GAS DISPENSING TO FRY'S STORE |
|
02/29/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 601-721-2548 |
|
02/27/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* - OK U.G FOR SIGN & LIGHT POLES - CALL FOR LIGHT POLE BASES WHEN READY |
|
02/26/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* - CONDUIT DEPTH IN ROADWAYS & PARKING MUST BE MIN. 2' DEEP PER 300.5 NEC - OK NORTH - BLACK NON-METALLIC PIPING USED FOR COMM. DATA NOT LISTED OR MARKED 354.6 & 356.6, 110.3 ALSO, SHOULD BE MARKED ON CONDUIT |
|
02/20/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* - OK SECONDARY TO PULL BOX FROM KIOSK TO TEP PAD - COMMUNICATION CONDUITS UNDER PARKING LOT TO EXISTING STORE NOT MARKED, PROVIDE INFO ON LISTING |
|
01/28/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK UNDERGROUND FOR KIOSK & DISPENSING AREAS |