Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03404
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE PERMANENT CIRCUIT DIRECTORY FULLY FILLED OUT - CORRECT LABELING NEEDED 2. CLEAN EXCESS DIRT FROM PANEL 3. ONLY ONE CONDUCTOR TO TERMINAL AT BREAKER 4. VERIFY DERATING OF CONDUCTORS PER 310.15 5. BOND MAIN DISCONNECT ENCLOSURE 6. SUPPORT VDV CABLING AS PER 725.6 & 300.11 7. MANUFACTURES HOLDDOWN NEEDED FOR MAIN BREAKER -- 408.16 8. WATER HEATER CIRCUIT NOT AS PER PLANS 9. SERVICE NOT AS PER PLAN - PLANS CALL FOR NEW 10. MOUNT EXTENSION BOX TO WALL BOX NOT WALL WITH APPROVED HARDWIRE 11. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 12. PLEASE VERIFY BOX FILL WITH CONTACTORS 13. VERIFY GROUNDING ELECTRODE CONDUCTOR FOR TRANSFORMER |