Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03404

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE PERMANENT CIRCUIT DIRECTORY FULLY FILLED OUT - CORRECT LABELING NEEDED
2. CLEAN EXCESS DIRT FROM PANEL
3. ONLY ONE CONDUCTOR TO TERMINAL AT BREAKER
4. VERIFY DERATING OF CONDUCTORS PER 310.15
5. BOND MAIN DISCONNECT ENCLOSURE
6. SUPPORT VDV CABLING AS PER 725.6 & 300.11
7. MANUFACTURES HOLDDOWN NEEDED FOR
MAIN BREAKER -- 408.16
8. WATER HEATER CIRCUIT NOT AS PER PLANS
9. SERVICE NOT AS PER PLAN - PLANS CALL FOR NEW
10. MOUNT EXTENSION BOX TO WALL BOX NOT WALL WITH APPROVED HARDWIRE
11. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
12. PLEASE VERIFY BOX FILL WITH CONTACTORS
13. VERIFY GROUNDING ELECTRODE CONDUCTOR FOR TRANSFORMER