Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION |
|
| 11/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER TO NIPPLE TO BE #2 NEC 250.102 & 250.66 2. INSTALL PROTECTIVE BUSHING ON CONNECTORS OF CONDUCTORS #4 & LARGER - NEC 300 3. HAVE APPROVED PLANS ON SITE |
|
| 11/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK GROUND RING 2) OK 2" PVC FROM SES TO CABINET 3) INSTALL CLASS J FUSES PER PLAN 4) RECALL FOR FINAL WHEN ALL WORK COMPLETE |