Permit: T07CM03397

Parcel: 114600830

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03397

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
THIS IS A ONE TIME ONLY ALLOWANCE FOR FIRE CAULK TO FULFILL THE REQUIREMENTS AT PANELS
11/10/2007 ELECTRIC - FINAL Partial Approval 1. BOXES MORE THAN 1/4" - 314.20
2. PANEL MORE THAN 1/4" - 408.2 & 314.20
3. LABEL CIRCUIT DIRECTORY PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
4. USE TERMINAL END WITH STRANDED CONDUCTORS AT SCREWS
5. MOUNT WIRE MOLD TO FLOOR AS PER PLANS

OK ROOF

MATT HAS MONEY ORDER
RECEIVED LETTER FOR FLEX CONDUIT
11/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
NO POWER