Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03397
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL THIS IS A ONE TIME ONLY ALLOWANCE FOR FIRE CAULK TO FULFILL THE REQUIREMENTS AT PANELS |
|
11/10/2007 | ELECTRIC - FINAL | Partial Approval | 1. BOXES MORE THAN 1/4" - 314.20 2. PANEL MORE THAN 1/4" - 408.2 & 314.20 3. LABEL CIRCUIT DIRECTORY PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER 4. USE TERMINAL END WITH STRANDED CONDUCTORS AT SCREWS 5. MOUNT WIRE MOLD TO FLOOR AS PER PLANS OK ROOF MATT HAS MONEY ORDER RECEIVED LETTER FOR FLEX CONDUIT |
|
11/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED NO POWER |