Permit: T07CM03396

Parcel: 116155090

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03396

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/26/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE VOLUME DAMPERS IN ALL SUPPLY BRANCH COLLARS
2. PROPERLY DUCT SEAL ALL START COLLARS
3. DUCT SEAL ALL S&D JOINTS INCLUDING END CAPS
4. AC-2: R/A GRILL TOO CLOSE TO SUPPLY SEE PLANS INSTALL PER REFLECTED
5. ALL SUPPORT STRAPS TO HAVE 1 SCREW IN BOTTOM AND 2 IN SIDES