Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/26/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE VOLUME DAMPERS IN ALL SUPPLY BRANCH COLLARS 2. PROPERLY DUCT SEAL ALL START COLLARS 3. DUCT SEAL ALL S&D JOINTS INCLUDING END CAPS 4. AC-2: R/A GRILL TOO CLOSE TO SUPPLY SEE PLANS INSTALL PER REFLECTED 5. ALL SUPPORT STRAPS TO HAVE 1 SCREW IN BOTTOM AND 2 IN SIDES |