Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07CM03394
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
11/01/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PANELS LOCKED - PLEASE RECALL INSPECTION, UNCOVER PANELS FOR INSPECTION |
|
09/26/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* - PLAN SHOWS EXISTING 60 AMP SERVICE CONTR. INSTALLED 100 AMP - ALSO, BOND GROUND AT BOND BUSHING TO ENCLOSURE - SEE NOTES PREVIOUS INSP. |
|
09/25/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. GROUNDING ELECTRODE SYSTEM MUST BE TIED TOGETHER TO FORM A COMMON SYSTEM FOR MULTIPLE SERVICES ON SAME BLD. 250 NEC 2. NO LOADS CONNECTED 3. NEUTRALS TO BE BONDED IN SERVICE DISCONNECTS PER 250 NEC 4. BOND GAS PIPING 5. YOU WILL NEED TO INSTALL LABEL TO INDICATE HIGH LEG 6. 100 AMP SERVICE NOT SHOWN ON PLAN 7. OK RESTROOM WALLS |
|
09/21/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |