Permit: T07CM03387

Parcel: 12706010A


Addresses:

40 N SWAN RD 01


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03387

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
02/19/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SOME CONDENSATE LINES DO NOT HAVE THE
MIN. 1/8" PER FT. SLOPE
INSULATE DRAIN LINES AS PER PLANS
11/07/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- RELOCATE 2 KINKED FLEX DUCTS 1ST FLOOR
- SUPPLY & EXHAUST 1ST FLOOR RESTROOMS OK TO SHEETROCK
- OK FOR CEILING TILES 1ST FLOOR