Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03387
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING 2. FINISH OUTLET 314.21 |
|
02/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF 1. SUPPORT CONDUIT FOR T-STAT 2. LOOSE FITTINGS DOWNSTAIRS: 1. EM/EXIT LIGHTS EAST TO BE AS PER 700.12 2. WHAT IS 30 AMP. SINGLE POLE BREAKER FOR 3. MISSING PANEL HARDWARE PANEL? - MARK PANELS ON OUTSIDE COVERS 4. LABEL ALL BREAKERS 5. FINISH PREVIOUS ITEMS UPSTAIRS: 1. BOND WATER HEATER DISCONNECT ENCLOSURE & TIGHTEN LOOSE FITTINGS 2. MISSING PANEL HARDWARE PANEL? MARK PANELS ON OUTSIDE COVERS 3. RECEPTACLES & LIGHTS TO WHERE 408.4 4. FINISH VDV CABLING AS PER 725.6, 800.24 5. BOXES MORE THAN 1/8" AROUND 314.21 ROOF: 1. LABEL DISCONNECTS 2. PROTECT SEALTITE FROM SHARP METAL EDGES 3. USE CORRECT COLORS FOR CONDUCTORS 210.5(C) AMENDMENTS |
|
02/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |