Permit: T07CM03387

Parcel: 12706010A


Addresses:

40 N SWAN RD 01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03387

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH VDV CABLING
2. FINISH OUTLET 314.21
02/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF
1. SUPPORT CONDUIT FOR T-STAT
2. LOOSE FITTINGS

DOWNSTAIRS:
1. EM/EXIT LIGHTS EAST TO BE AS PER 700.12
2. WHAT IS 30 AMP. SINGLE POLE BREAKER FOR
3. MISSING PANEL HARDWARE PANEL? - MARK PANELS ON OUTSIDE COVERS
4. LABEL ALL BREAKERS
5. FINISH PREVIOUS ITEMS

UPSTAIRS:
1. BOND WATER HEATER DISCONNECT ENCLOSURE & TIGHTEN LOOSE FITTINGS
2. MISSING PANEL HARDWARE PANEL? MARK PANELS ON OUTSIDE COVERS
3. RECEPTACLES & LIGHTS TO WHERE 408.4
4. FINISH VDV CABLING AS PER 725.6, 800.24
5. BOXES MORE THAN 1/8" AROUND 314.21

ROOF:
1. LABEL DISCONNECTS
2. PROTECT SEALTITE FROM SHARP METAL EDGES
3. USE CORRECT COLORS FOR CONDUCTORS 210.5(C) AMENDMENTS
02/04/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*