Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/04/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) UPSTAIRS: PANEL SCHEDULES TO BE PER 408.4-NO ABREVIATIONS 2) CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 3) IDENTIFY GROUNDING CONDUCTOR AT TERMINALS 4) MOTION SWITCHES NOT WORKING 5) EM LIGHT NOT WORKING |
|
| 01/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE 1. OK TO CHECK LAST 2 ROOMS ON FINAL |
|
| 01/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR 1. SUPPORT WIRE NEEDED ON EXIT SIGN - EAST HALL 2. PROTECT PVC AT BASE PLATE OK TO TILE 1ST FLOOR EXCEPT AS NOTED 2ND FLOOR 1. MANUFACTURES CLIPS TO BE EFFECTIVE 2. NO MORE THAN 360 DEG. IN A RUN |
|
| 01/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. WHAT IS EXPOSED CONDUCTOR & HANGING CONDUIT 2. FINISH ROOM STOAGE, EAST HALL EXIT 3. FINISH TAP BOX OK TO TILE EXCEPT AS NOTED |
|
| 01/03/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLOSE ALL OPEN JUNCTION BOXES 2. CHECK FIXTURES SECURED TO GRID |
|
| 11/21/2007 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 11/13/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |