Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03387
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. HAVE BUILDING INSPECTOR VERIFY FIRESTOPPING BETWEEN FLOORS 2. MAINTAIN WORKING CLEARANCES AT OUTSIDE DISCONNECTS - 110.26 OK 2 1/2" CONDUIT BOTTOM PANEL TO TOP PANEL |
|
11/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANEL WALL 1ST FLOOR 2) OK WALLS 2ND FLOOR 3) OK HARD LIDS RESTROOMS 2ND FLOOR |
|
09/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT PANEL WALLS |
|
09/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C TOP PLATE & ACROSS STUDS 2. USE APPROVED STRAPS FOR MC CABLE 3. SUPPORT CONDUIT AS PER CODE 4. TIGHTEN LOOSE FITTINGS 5. PANEL WALL NOT DONE AT THIS TIME |