Permit: T07CM03382

Parcel: 114600830

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03382

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
TESTED HOOD HEAT SENSOR
AIR BALANCE OK
ALL CORRECTIONS HAVE BEEN MADE
02/07/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- REVISE DRAWINGS TO SHOW ELECTRICAL CIRCUITRY TO EXHAUST FAN HEAT SENSOR CONTROL BOX.
- NEED TO TEST HEAT SENSOR FOR FINAL
- PAINT BLACK IRON DUCT ON ROOF.
- PROVIDE A CLEANOUT FOR HORIZONTAL DUCT
- USE A LISTED FLEX CONNECTOR TO EXHAUST FAN
- TESTED DUCT SMOKE DETECTORS
- SEE BLDG. INSPECTOR FOR TEMP C OFO