Permit: T07CM03382

Parcel: 114600830

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T07CM03382

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
CHECKED 2ND LAYER OF FIRE WRAP
RESUPPORT PIPES THAT HAVE HANGERS REMOVED
01/15/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
- CHECKED 1ST LAYER OF FIRE WRAP
- OK TO INSTALL 2ND LAYER REQUIRED BY ASTM TEST STANDARD E2336
- SEE SECTION 506.3.10 EXCEPTIONAL 1-2006 IMC
01/14/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
SOME BANDING NOT PER INSTALL INSTRUCTIONS MUST BE WITHIN 1 1/2" OF EDGE OF WRAP AND MUST HAVE MIN. 3' OVERLAPS ON JOINTS.
12/31/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
GREASE DUCT TOUCHING WOOD STRUCTURE - OVEN
CURB NOT PROPERLY INSTALLED - OVEN
OK TO INSULATE DUCT
12/14/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO PROCEED
SUPPLY & EXHAUST IN RESTROOMS OK TO SHEETROCK HARD LIDS AND SOFFITS