Permit: T07CM03382

Parcel: 114600830

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM03382

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/28/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CORRECT SLOPE OF VENT AT TERMINATION IN
CORRECT PIPE INSULATION AT REPAIR
CLOSET FLANGES NOT READY
12/19/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
REDLINES OK
APPROVED PLAN REQUIRED FOR APPROVAL
12/14/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
REDLINE CHANGES TO GAS SYSTEM ON APPROVED PLAN
PSI TEST ON BOTH SYSTEMS OK
SAFETY PLATES REQUIRED ON ALL PIPING
TWO HOLE STRAPS REQUIRED ON ALL PIPING
12/12/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPE INSULATION OK TO COVER
CORRECTIONS OK
12/06/2007 PLUMBING - INTERMEDIATE Partial Approval DWV W/TEST THRU ROOF OK
PROVIDE ACCESS TO CLEANOUT AT P-2
CONNECT VENT AT K107
OK TO INSULATE HW PER PLAN
70 PSI TEST ON WATER PIPING