Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/06/2008 | ELECTRIC - FINAL | Partial Approval | ||
| 02/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" OR 1/8" AROUND 314.20 & 314.21 OR FLUSH AT COMBUSTIBLES 2. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS 3. SEALING FOR 300.7 AT WALK-IN BOXES TO BE NON-COMBUSTIBLE 4. A WET LOCATION COVER NEEDED AT DISHWASHER ROOF: 1. TIGHTEN LOOSE FITTINGS 2. PROTECT SEALTITE FROM SHARP METAL EDGES 3. IDENTIFY CONDUCTOR ENTIRE EXPOSED LENGTH |