Permit: T07CM03382

Parcel: 114600830

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03382

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH BELL ENDS
01/23/2008 ELECTRIC - INTERMEDIATE Partial Approval 1. POST BOND FOR TEMP POWER
2. ALL DEVICES 8' AND BELOW TO BE INSTALLED AND PLATED
3. PROTECT CONDUCTORS AT CONDUITS 352.46 & 300.4

OK PANEL CONNECTIONS
01/18/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
LOCKED NO ACCESS 5:50 PM
12/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & LIDS
12/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT END OF CONDUITS FOR VDV CABLING FROM SHARP EDGES
2. SUPPORT MC CABLE WITHIN 12" OF CANS
3. USE HARDWARE ADEQUATE TO HOLD BOXES IN CEILING
4. CAP UNUSED PVC CONDUIT - PANEL
5. SUPPORT CONDUIT ABOVE PANEL
*JUNCTION BOXES TO BE ACCESSIBLE
6. PROTECT MC CABLE AT SHALLOW STUDS
7. SUPPORT VDV CABLING ON HARD CEILINGS
12/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ONE SIDE PONY WALLS AND BEVERAGE STATION

1. MC CABLE TO TERMINATE
2. VERIFY WET LOCATION LISTING FOR MC CABLE
3. SUPPORT MC CABLE WITHIN 12" OF BOXES
4. PREVENT DIEELECTRIC CONTACT
5. PROTECT PVC CONDUIT AT BASE PLATES
6. PULL IN VDV CABLING