Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03379
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FLEX IS NOT AN APPROVED METHOD FOR 517.13 OK WALLS |
|
09/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLOSE ALL OPEN JUNCTION BOXES IN CEILING 2. SEAL ALL OPEN KNOCKOUTS IN RECEPT OUTLET BOXES 3. ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS TO MEET REQUIREMENT OF 517.13 THIS INCLUDES SWITCHES. |
|
08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE VERIFY EXISTING OUTLET IN PATIENT CARE MEET REQUIREMENTS OF 517.13 OK WALLS |