Permit: T07CM03379

Parcel: 12709001E


Addresses:

535 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03379

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLEX IS NOT AN APPROVED METHOD FOR 517.13

OK WALLS
09/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CLOSE ALL OPEN JUNCTION BOXES IN CEILING
2. SEAL ALL OPEN KNOCKOUTS IN RECEPT OUTLET BOXES
3. ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS TO MEET REQUIREMENT OF 517.13 THIS INCLUDES SWITCHES.
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE VERIFY EXISTING OUTLET IN PATIENT CARE MEET REQUIREMENTS OF 517.13

OK WALLS