Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 OF PREVIOUS INSPECTION |
|
| 09/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11 2. PLEASE SUPPORT M/C CABLE INDEPENDENTLY 300.11 |