Permit: T07CM03346

Parcel: 117160220


Addresses:

200 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03346

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR TO RESCHEDULE FOR 7:30-8:00 1ST STOP AND HAVE EQUIPMENT OPEN FOR INSPECTION
06/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY GLEN @ QUALIFIED ELECTRIC
06/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR TO RECLOSE ALL EQUIPMENT

AT MSB-B
1. PROVIDE PROPER GROUND BAR TO TERMINATE ALL EQUIPMENT GROUNDS - NEUTRALS & GROUNDS TO BE SEPARATED
2. SEAL ALL OPENINGS - AND REPLACE MISSING PANELS
3. REPLACE MISSING SCREWS

AT SERVICE
1. PROPERLY IDENTIFY CKT'S (AS ON PLANS) AT BREAKERS AND EQUIPMENT AT OTHER END
2. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH
3. PROVIDE SERVICE INSTALLATION MANUAL TO CONFIRM OVERHEAD FEED. FEEDER CONDUCTORS ARE LAYING ON BUSS AND SHARP METAL EDGES

ON ROOF -
1. SIDE WALL 3/4 L.B INTO J-BOX LOOSE COVER
MISSING GASKET
2. SECURE ALL RACEWAYS TO STRUCTURE - NOT JUST BLOCKS
3. REMOVE ALL PAINT UNDER LUGS IN J-BOX MCC
4. NEED SERVICE RECEPTACLE WITHIN 25' AND SAME LEVEL AS HVAC (GFI) EQUIP.
5. VERIFY PROPER TYPE CHILLER FUSES IN MCC
6. PANEL PH
1. PROPERLY IDENTIFY
2. LOADS NOT PER PLAN
3. NEUTRAL AND GROUND #6 & SMALLER TO BE WHITE/GREEN ENTIRE LENGTH

PARTIAL INSPECTION ONLY -
GO THROUGH MAKE PER PLAN/CODE
06/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EQUIPMENT TO BE OPEN FOR INSPECTION
06/04/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WILL RESCHEDULE INSPECTION WHEN ELECTRICAL CONTRACTOR CAN BE ON SITE TO OPEN EQUIPMENT.
05/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ELECTRICIAN & CONTRACTOR ON SITE TO INSPECT

*LAST INSPECTION BY THIS INSPECTOR THE BUILDING WAS UNDER CONST. IT IS NOW OCCUPIED.