Permit: T07CM03346

Parcel: 117160220


Addresses:

200 N STONE AV


Inspection Status: Not Applicable

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07CM03346

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Not Applicable

Date Description Inspector Results Comments
06/04/2008 ELECTRIC - CABLE DROP Not Applicable IVRS - Inspection :*
05/21/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/25/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) CALL FOR FOLLOW UP AFTER TEP TIE IN
12/31/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
WALKED JOB - NO ONE PRESENT
12/19/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
1. PROVIDE GROUNDING ELECTRODE FOR SERVICE - NEC 250
2. BOND ALL PIPING SYSTEMS TO SERVICE - NEC 250
3. PROVIDE ILLUMINATION FOR SERVICE - NEC 110
4. PROVIDE TORQUE LETTER - NEC 110
5. MAINTAIN 6' DEDICATED SPACE ABOVE SERVICE - NEC 110
6. PROVIDE PANIC HARDWARE FOR EXIT DOOR - NEC 110
7. SECURE SERVICE RACEWAYS WITHIN 3' OF SERVICE
8. SECURE SERVICE TO SLAB - NEC 110
9. BOLT GROUND BAR THROUGH - NEC 250
10. BOND SERVICE RACEWAYS AND SERVICE RACEWAY
TO J-BOX - NEC 250, NEC 250.96, 250.102
12/14/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
12/12/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
PLANS TO BE ON SITE