Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T07CM03346
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Not Applicable
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2008 | ELECTRIC - CABLE DROP | Not Applicable | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/25/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) CALL FOR FOLLOW UP AFTER TEP TIE IN |
|
12/31/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* WALKED JOB - NO ONE PRESENT |
|
12/19/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* 1. PROVIDE GROUNDING ELECTRODE FOR SERVICE - NEC 250 2. BOND ALL PIPING SYSTEMS TO SERVICE - NEC 250 3. PROVIDE ILLUMINATION FOR SERVICE - NEC 110 4. PROVIDE TORQUE LETTER - NEC 110 5. MAINTAIN 6' DEDICATED SPACE ABOVE SERVICE - NEC 110 6. PROVIDE PANIC HARDWARE FOR EXIT DOOR - NEC 110 7. SECURE SERVICE RACEWAYS WITHIN 3' OF SERVICE 8. SECURE SERVICE TO SLAB - NEC 110 9. BOLT GROUND BAR THROUGH - NEC 250 10. BOND SERVICE RACEWAYS AND SERVICE RACEWAY TO J-BOX - NEC 250, NEC 250.96, 250.102 |
|
12/14/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
12/12/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* PLANS TO BE ON SITE |