Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03341
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2010 | ELECTRIC - INTERMEDIATE | Approved | ||
09/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CALLED CLEARANCE INTO OFFICE TODAY |
|
08/31/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR FOR SES HAS BEEN CUT AND TAKEN (VADELS) 2) BOND BUSHINGS OF BONDING LOCK NUTS REQUIRED ON SUPPLY SIDE OF SERVICE. GROUNDING ELECTRODE CONDUCTOR TO BOND SERVICE, SIZE PER 250.66 NEC 3) OK WORK IN BLDG #1 4) EXISTING GROUNDING ELECTRODE SYSTEM HAS BEEN CUT FOR BOTH SERVICES-VERIFY WATER AND GAS PIPING |
|
07/13/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SOFFITS AT OUTSIDE FRONT VANS |