Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
| 08/28/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL |
|
| 08/21/2007 | MECHANICAL - FINAL | Denied | 1. CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP 2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON FAN COIL 3. INSULATE SHEET METAL SLEEVE ON TOP OF FAN COIL 4. REMOVE OR RAISE SHEET METAL COVER ON ROOF CAUSING WATER TO DAM 5. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 6. REINSTALL T&P DRAIN LINE WITH FITTINGS INTENDED FOR PROPER USE. REMOVE UNNECESSARY ELBOW 7. MARK UNIT DATA PLATE & FUSE ACCORDINGLY 8. PROPERLY I.D CIRCUIT BREAKERS |
|
| 08/14/2007 | MECHANICAL - FINAL | Partial Approval | NEED TO RAISE A/C LINE, REMOVE ALL SCREWS AND SEAL ALL PENETRATIONS |