Permit: T07CM03330

Parcel: 12311234B


Addresses:

1250 E SENECA ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03330

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
ALL CORRECTIONS HAVE BEEN MADE
08/28/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) RECALL
08/21/2007 MECHANICAL - FINAL Denied 1. CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP
2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON FAN COIL
3. INSULATE SHEET METAL SLEEVE ON TOP OF FAN COIL
4. REMOVE OR RAISE SHEET METAL COVER ON ROOF CAUSING WATER TO DAM
5. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
6. REINSTALL T&P DRAIN LINE WITH FITTINGS INTENDED FOR PROPER USE. REMOVE UNNECESSARY ELBOW
7. MARK UNIT DATA PLATE & FUSE ACCORDINGLY
8. PROPERLY I.D CIRCUIT BREAKERS
08/14/2007 MECHANICAL - FINAL Partial Approval NEED TO RAISE A/C LINE, REMOVE ALL SCREWS AND SEAL ALL PENETRATIONS