Permit: T07CM03325

Parcel: 10510010D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03325

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
02/12/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE SPRING ISOLATORS PER 2/M1.2
- PROVIDE SECONDARY DRAIN PANS PER 2/M1.2
- INSULATE CONDENSATE PIPING PER HVAC SPECS 2.01
- PROVIDE P-TRAPS PER HVAC SPECS 2.01
- REMOVE ABANDONED FIRE DAMPERS FROM SYSTEM
- PROVIDE HIGH EFFICIENCY TAKE OFFS ON NEW SYSTEMS
PER 1/M1.3