Permit: T07CM03321

Parcel: 126080290


Addresses:

4106 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
10/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #7, 8, 10 & 11 PREVIOUS INSPECTION
09/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SWITCHES IN SHOWER
2. LIGHT IN SHOWER TO BE FOR WET LOCATION
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
4. USE APPROVED HARDWARE TO MOUNT DEVICES - NOT DRYWALL SCREWS
5. ALL OUTLETS & OPENING IN BEDROOM TO BE ARC FAULT PROTECTED - INC. SMOKE DETECTORS
6. USE APPROVED FITTINGS FOR TANKLESS WATER HEATER
7. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
8. SUPPORT CONDUIT ON SIDE OF PANEL
9. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO
10. PLANS SHOW CIRCUITS FROM SUB-PANELS NOT ALL IN ONE
11. PLANS NOT REFLECTIVE OF EM & EXIT LIGHTS