Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 10/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #7, 8, 10 & 11 PREVIOUS INSPECTION |
|
| 09/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SWITCHES IN SHOWER 2. LIGHT IN SHOWER TO BE FOR WET LOCATION 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 4. USE APPROVED HARDWARE TO MOUNT DEVICES - NOT DRYWALL SCREWS 5. ALL OUTLETS & OPENING IN BEDROOM TO BE ARC FAULT PROTECTED - INC. SMOKE DETECTORS 6. USE APPROVED FITTINGS FOR TANKLESS WATER HEATER 7. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 8. SUPPORT CONDUIT ON SIDE OF PANEL 9. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 10. PLANS SHOW CIRCUITS FROM SUB-PANELS NOT ALL IN ONE 11. PLANS NOT REFLECTIVE OF EM & EXIT LIGHTS |