Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM03320
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
11/08/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DO NOT USE FSK TAPE TO SEAL EXHAUST DUCT CONNECTIONS USE APPROVED DUCT SEALER DO NOT USE NYLON STRAPPING TO SUPPORT ALUMINUM FLEX FLEX DUCTING NOT INSTALLED PER DETAIL ON PLANS OK PARTIAL TILES AIR BALANCE REPORT OK |
|
10/19/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS OK FOR SHEETROCK |