Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 11 PSI |
|
| 08/17/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TEST TO HOLD WITH NO LOSS OF PRESSURE 2. PROVIDE TEST GAUGE IN 1/10TH POUND INCREMENTS 3. PROVIDE AGA OR CSA APPROVED 1/2" GAS VALVE AT WATER HEATER |
|
| 08/14/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* NOT HOLDING TEST REPAIR LEAK BEFORE CALLING FOR INSPECTION |
|
| 08/13/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) TEST SHALL HOLD WITH NO LOOS OF PRESSURE FOR 15 MINUTES 2) PLEASE CAP ALL VALVE LOCATIONS THAT ARE NOT IN USE |