Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03302
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" 314.20 2. POWER POLES - FILL UNUSED OPENING IN BOX, SUPPORT M/C CABLE 12" 3. CLEAN SURFACE UNDER LUGS 250.12 ALSO, DO NOT STACK 4. LABEL DISCONNECTS & TRANSFORMER 5. PANEL SCHEDULES TO BE AS PER 408.4 NO ABBREVIATIONS 6. BOND GUTTERS 7. CONNECT SEPARATELY DERIVED SYSTEMS TO BUILDING STEEL OK ENTRY HALL & DRINKING FOUNTAIN |