Permit: T07CM03302

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" 314.20
2. POWER POLES - FILL UNUSED OPENING IN BOX, SUPPORT M/C CABLE 12"
3. CLEAN SURFACE UNDER LUGS 250.12 ALSO, DO NOT STACK
4. LABEL DISCONNECTS & TRANSFORMER
5. PANEL SCHEDULES TO BE AS PER 408.4 NO ABBREVIATIONS
6. BOND GUTTERS
7. CONNECT SEPARATELY DERIVED SYSTEMS TO BUILDING STEEL

OK ENTRY HALL & DRINKING FOUNTAIN