Permit: T07CM03302

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/25/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/24/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
10/01/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/28/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. VDV CABLING TO BE SUPPORTED AS PER 300.11
2. FIXTURE IN HALL WITH BROKEN PARTS - EXPOSED METAL CONTACTS - OPEN BOXES
3. VERIFY HALL FOUNTAIN - DO NOT CLOSE
09/26/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH EXIT LIGHTS
2. FILL UNUSED OPENINGS
3. FINISH VDV CABELING & AS PER 300.11, 725.3 & 6
4. CHECK BOX FILL
5. IF USING SCREWS FOR 2X4'S 4 ON CORNERS OR 2 ON CENTER
6. ATTACH FIXTURES TO GRID 410.16 (HALL) ALSO BROKEN PARTS
7. PLEASE VERIFY ELECTRICAL FOR HALL FOUNTAIN
8. OPEN BOXES IN HALL