Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM03302
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
10/01/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/28/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. VDV CABLING TO BE SUPPORTED AS PER 300.11 2. FIXTURE IN HALL WITH BROKEN PARTS - EXPOSED METAL CONTACTS - OPEN BOXES 3. VERIFY HALL FOUNTAIN - DO NOT CLOSE |
|
09/26/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH EXIT LIGHTS 2. FILL UNUSED OPENINGS 3. FINISH VDV CABELING & AS PER 300.11, 725.3 & 6 4. CHECK BOX FILL 5. IF USING SCREWS FOR 2X4'S 4 ON CORNERS OR 2 ON CENTER 6. ATTACH FIXTURES TO GRID 410.16 (HALL) ALSO BROKEN PARTS 7. PLEASE VERIFY ELECTRICAL FOR HALL FOUNTAIN 8. OPEN BOXES IN HALL |