Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/12/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO WRAP DUCT |
|
| 12/10/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TOP OF DUCT NOT SEALED ALL JOINTS NOT SEALED SEAL DUCT AT FURNACES FLUE PIPE NOT RUN DUCT NOT PROPERLY FASTENED WITH DRAINS |
|
| 12/03/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO PROCEED |
|
| 11/30/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PROVIDE DUCT TO OUTSIDE IN RESTROOMS ON EXHAUST FANS. - SEAL ALL DUCT WORK JOINTS ABOVE CEILING - PATCH DUCTWORK THROUGH WALLS - PER GENERAL NOTE "7" M-2 PROVIDE VIBRATION ISOLATORS - REFER TO ALL NOTES AND SPECS DURING INSTALLATION |