Permit: T07CM03301

Parcel: 11706195A


Addresses:

33 S 6TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/07/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
12/12/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO WRAP DUCT
12/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
TOP OF DUCT NOT SEALED
ALL JOINTS NOT SEALED
SEAL DUCT AT FURNACES
FLUE PIPE NOT RUN
DUCT NOT PROPERLY FASTENED WITH DRAINS
12/03/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO PROCEED
11/30/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- PROVIDE DUCT TO OUTSIDE IN RESTROOMS ON
EXHAUST FANS.
- SEAL ALL DUCT WORK JOINTS ABOVE CEILING
- PATCH DUCTWORK THROUGH WALLS
- PER GENERAL NOTE "7" M-2 PROVIDE VIBRATION ISOLATORS
- REFER TO ALL NOTES AND SPECS DURING INSTALLATION