Permit: T07CM03298

Parcel: 124071020

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03298

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/13/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/09/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/19/2007 MECHANICAL - FINAL Cancelled
10/12/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PAINT CONDENSATE PIPE W/LATEX PAINT
ATTACH DISCONNECT BOX
SEAL ROOF JACK AT G.F.I
NEED FILTER IN R/A GRILL
PROPERLY INSTALL T-STAT
FINISH INSTALLING BATHROOM EXHAUST FAN
INSTALL SUPPLY GRILLS
10/09/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED LADDER FOR ROOF ACCESS PLEASE RECALL
08/09/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE A CONDENSATE DRAIN LINE
- PROPERLY IDENTIFY CONDUCTORS USED TO POWER THE DISCONNECT.
- PROVIDE A GFI SERVICE RECEPTACLE ON ROOF
- RELOCATE SLEEPERS TO SPAN ROOF JOISTS