Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
Permit Number - T07CM03289
Inspection Description - MECHANICAL - HOOD SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2008 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection :* | |
04/04/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1. GREASE DUCT NOT PROPERLY ATTACHED TO CURB 2. ALL PVC CONDENSATE PIPING ON ROOF TO BE PAINTED WITH LATEX PAINT 3. PROVIDE FILTERS IN OUTSIDE AIR INLETS |
|
03/11/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* GREASE DUCT WRAP OK |
|
03/03/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* PROVIDE INTERLOCK SYSTEMS PROVIDE GREASE DUCT LEAK TEST |