Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* REFER TO DETAIL M-2 101 FOR HANGER APPLICATION IN REGRESS TO FLEX DUCT SPECIFICALLY 24 GA. STRAPS AND 12" SADDLES |
|
| 03/03/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* REMOVE NYLON STRAP SUPPORTING FLEX TO SPRINKLER PIPE ALL FLEX OVER 10" TO BE SUPPORTED WITH STRAP NOT GRID WIRE PROVIDE SUPPORT ON FLEX INDICATED ON SITE DRAWINGS |