Permit: T07CM03289

Parcel: 10605001B


Addresses:

3979 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03289

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORDS FOR PENDANT RECEPTACLES NOT TO PASS THROUGH CEILING AND NEED GFI PROTECTION
2. PANEL DIRECTORY NOT CORRECT
3. MAX OVERCURRENT PROTECTION FOR WALK IN
FAN COILS 15 AMP -- SEE DATA PLATE & VERIFY

ON ROOF:
1. PROPERLY IDENTIFY WHITE USED AS HOT
2. PROPERLY IDENTIFY DISCONNECTS
3. SECURE CONDENSOR TO ROOF
4. NEED GFI PROTECTED/WORKING SERVICE RECEPTACLE

ALSO - CHECK FRONT EMERGENCY