Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03289
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORDS FOR PENDANT RECEPTACLES NOT TO PASS THROUGH CEILING AND NEED GFI PROTECTION 2. PANEL DIRECTORY NOT CORRECT 3. MAX OVERCURRENT PROTECTION FOR WALK IN FAN COILS 15 AMP -- SEE DATA PLATE & VERIFY ON ROOF: 1. PROPERLY IDENTIFY WHITE USED AS HOT 2. PROPERLY IDENTIFY DISCONNECTS 3. SECURE CONDENSOR TO ROOF 4. NEED GFI PROTECTED/WORKING SERVICE RECEPTACLE ALSO - CHECK FRONT EMERGENCY |