Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM03289
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SEAL UNUSED OPENINGS IN EQUIPMENT (J BOXES & RACEWAYS) - NEC 110 2. CEILING GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT OTHER EQUIPMENT - NEC 300.11 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS OK TILES AFTER CORRECTIONS EXCEPT @ CONTACTOR J-BOX |
|
02/11/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/21/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |