Permit: T07CM03283

Parcel: 140552170

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/19/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/17/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWN BOLTS LOOSE
2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACE
3) NO PLAN ON SITE
4) STOPPED INSPECTION
09/13/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED CS SOUTH SIDE SECOND FLOOR AT SHEARWALL
2) EPOXY H/D NOT COMPLETE
3) 2ND FLOOR SHEAR AT STAIRS 3" ON CENTER ADD A35'S AT TOP PLATE
4) CHECK NAIL SPACING ALL SHEAR WALLS PER PLAN
5) CHECK RED HEADS AS REQUIRED