Permit: T07CM03282

Parcel: 140552180

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/28/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/25/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEAR TRANSFER CLIPS A35F TO BE AT EACH CORNER OF SHEAR THEN LAYOUT GARAGE
2) BLOCK SUPPORT UNDER POP OUT, 2ND FLOOR DOWN ON GARAGE ROOF
3) DBL STUD END STUD OUTSIDE CORNER 2ND FLOOR FRONT POP OUT CLIP STUD TO TOP PLATE
4) NO ACCESS TO ROOF
5) WRONG NAILS USED IN TRUSS TO GIRDER HANGERS HUS26 SHEAR NAILING TAKES A 3" LONG MIN. SINKER FACE NAIL 16D
6) PLANS CALL FOR #5 SHEAR 2ND FLOOR BED 3, NO #5 ON SHEAR SCHEDULE