Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK PLUMBING FINAL OK |
|
| 04/10/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. UNABLE TO LOCATE LETTER DELETING GAS 2. WATER HEATER REQUIRES EXPANSION TANK 3. ALL HOT & COLD PIPING WITHIN 8' OF WATER HEATER TO BE INSULATED 4. PUBLIC USE LAVATORIES REQUIRE MIXING VALVES 5. TRAP ARMS MAY NOT BE REDUCED - TRAP AND TRAP ARM TO BE THE SAME SIZE - TRAP MAY BE ONLY ONE SIZE LARGER THAN TAILPIECE OF FIXTURE 6. KITCHEN SINK NOT CAULKED - CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE - MAY NOT BE A COMPLETE LIST - HAVE PLUMBER CHECK ALL WORK - WILL REQUIRE CLEAN BACTERIA REPORT FOR NEXT INSPECTION |
|
| 04/08/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* DOOR LOCKED -- NO ACCESS |